Modbus RTU Frames

RTU Frames is an offline request builder and reply inspector. It builds one eight-byte read request for function 01 (coils), 02 (discrete inputs), 03 (holding registers), or 04 (input registers), with a low-byte-first CRC-16/MODBUS. It opens no serial port, sends no traffic, and writes no files. Request fields, reply text, and view choices survive Home in RAM and reset on reboot.

Prepare a read

  1. Choose a read function, unit 1-247, a zero-based address 0-65535, and count 1-16. The last address must stay at or below 65535. Broadcast unit 0, reserved units, writes, and automatic polling are unsupported.
  2. Tap COPY REQUEST. The preview shows the exact eight bytes and copies them to the shared byte clipboard. Invalid fields leave the previous clipboard untouched.
  3. Open Serial, select UART or onboard RS-485 and the device's baud/parity/stop settings, and tap PASTE. Paste selects Hex with no extra line ending. Review the bytes, tap START, then CAPTURE RX before SEND. After the expected reply arrives, tap FREEZE RX and COPY RX, then return here to PASTE REPLY and DECODE.

For example, unit 1, function 03, address 0, count 10 produces 01 03 00 00 00 0A C5 CD. A device manual's holding-register label 40001 commonly maps to protocol address 0; follow that device's addressing convention rather than entering the label automatically.

The frame tool does not implement a timed RTU transaction or detect frames in the Serial receive stream. Match serial framing to the device; the serial specification uses even parity with one stop bit by default, or two stop bits without parity. RTU also requires inter-character and inter-frame timing that this offline app cannot assess. Use the tablet as the only requester on a bus you manage. See the Modbus serial specification, sections 2.1 and 2.5.1 and pin safety.

Inspect a reply

Enter the entire captured reply as Hex, including the unit, function and final two CRC bytes. Complete byte pairs may be contiguous or separated by ASCII whitespace. PASTE REPLY accepts 1-37 bytes from the shared clipboard without decoding or changing request fields. Empty/absent or oversized copies preserve the current draft. Use Serial's frozen COPY RX window or prepare known bytes in Byte Lab's Hex mode. Serial collects raw bytes across reads without detecting frames: verify that the copied window includes exactly one whole reply and excludes any request echo.

Saved UART/RS-485 logs in Files also offer COPY ROW for a selected record of at most 128 bytes. A whole RTU read reply fitting the 37-byte inspector limit can be pasted here. Rows are saved chunks and are not combined automatically: a split reply needs all of its bytes, and a row containing echo or multiple frames needs inspection before use.

Tap DECODE to validate the reply against the current request. Normal replies must have the expected unit, function, count, exact length and CRC. Unused high bits in a final coil/discrete-input byte must be zero. Exception replies show the device's exception code and no old values. Corrupt, incomplete, oversized, concatenated, or mismatched replies produce an error. A bad reply does not stop you from copying a valid request.

The inspector shows raw unsigned/hex/signed 16-bit words, or paired unsigned/signed 32-bit and Float32 values in ABCD, CDAB, BADC or DCBA byte order. A/B are the first register's bytes; C/D are the next. An odd final register remains visible as unpaired. Coil/discrete-input replies always show bits. Longer results scroll inside the result box.

Read replies do not echo their starting address or carry a transaction ID. Displayed addresses come from your request fields; a matching CRC/unit/function/count cannot establish when, where, or in response to which request the bytes were captured. Editing any field clears the decoded values. DECODE interprets the bytes again using the edited request, and changing a value view never sends traffic.

EXAMPLE replaces the request and reply drafts with an offline function-03 response containing Float32 1.5 in ABCD order: 01 03 04 3F C0 00 00 F6 1B. It does not change the shared clipboard. CLEAR clears only the reply draft. Tap a field for numeric/Hex keys; Done or Cancel hides the keyboard without copying or sending.

Verification and remaining work

The pure modbus_rtu_test checks a known wire request and exception, an independent CRC calculation, every supported unit/function, address boundaries, all read quantities, every single-bit mutation in generated replies, truncation, trailing bytes, unused bits, and output clearing on failure. TCP and RTU share the read PDU decoder, with direct cross-envelope comparisons. Existing Modbus TCP and Byte Lab pure tests also pass after that refactor.

tools/test_modbus_rtu_ui.ps1 -Snapshots runs the real app and LVGL against the already-built Debug host library. It checks exact clipboard bytes, malformed fields, CRC/exception responses, maximum replies, bit views, result invalidation, keyboards, Unicode/excess-length retention, popup teardown, and eight Home/reopen cycles with unchanged free heap and live allocations. It compiles sequentially, starts no background workers, and refuses to rebuild a missing LVGL library. PPM snapshots are saved under build/modbus-rtu-ui/.

The ESP-IDF 5.4.2 firmware compiled and linked with one build job on 2026-09-29. On ST7121, the example decoded Float32 1.5, and COPY REQUEST -> Serial PASTE preserved 01 03 00 00 00 02 C4 0B while the port remained stopped. This was an offline handoff, with no serial transmission. The remaining panel, input-boundary and wired-fixture checks are in the hardware checklist. An automatic RTU transport remains separate work: it needs exclusive UART ownership, precise frame/error handling, bounded cancellation and turnaround checks on physical hardware.