| 1 | +select: |
| 2 | + - platform: modbus_controller |
| 3 | + use_write_multiple: true |
| 4 | + modbus_controller_id: ${modbus_controller_id} |
| 5 | + id: remote_mode |
| 6 | + name: "Remote mode" |
| 7 | + address: 1100 |
| 8 | + value_type: U_WORD |
| 9 | + optionsmap: |
| 10 | + "Disable": 0 |
| 11 | + "Enable remote mode 1": 1 |
| 12 | + "Enable remote mode 2": 2 |
| 13 | + "Enable remote mode 3": 3 |
| 14 | + |
| 15 | + - platform: modbus_controller |
| 16 | + use_write_multiple: true |
| 17 | + modbus_controller_id: ${modbus_controller_id} |
| 18 | + id: inverter_output_power_control_mode |
| 19 | + name: "Inverter output power control mode" |
| 20 | + address: 1104 |
| 21 | + value_type: U_WORD |
| 22 | + optionsmap: |
| 23 | + "Enable AC side control mode": 0 |
| 24 | + "Enable battery side control mode": 1 |
| 25 | + "Enable grid side control mode": 2 |
| 26 | + |
| 27 | + - platform: modbus_controller |
| 28 | + use_write_multiple: true |
| 29 | + modbus_controller_id: ${modbus_controller_id} |
| 30 | + id: battery_side_control |
| 31 | + name: "Battery side control" |
| 32 | + address: 1105 |
| 33 | + value_type: U_WORD |
| 34 | + optionsmap: |
| 35 | + "Power": 2 |
| 36 | + "SOC": 3 |
| 37 | + "Voltage+Current": 4 |
| 38 | + "Power+SOC": 5 |
| 39 | + |
| 40 | + - platform: modbus_controller |
| 41 | + use_write_multiple: true |
| 42 | + modbus_controller_id: ${modbus_controller_id} |
| 43 | + id: ac_power_control_mode |
| 44 | + name: "AC power control mode" |
| 45 | + address: 1106 |
| 46 | + value_type: U_WORD |
| 47 | + optionsmap: |
| 48 | + "3 phase together": 0 |
| 49 | + "Each phase independent": 1 |
| 50 | + |
| 51 | +number: |
| 52 | + - platform: modbus_controller |
| 53 | + use_write_multiple: true |
| 54 | + modbus_controller_id: ${modbus_controller_id} |
| 55 | + id: remote_mode_watchdog_time |
| 56 | + name: "Remote mode watchdog time" |
| 57 | + min_value: 10 |
| 58 | + step: 1 |
| 59 | + address: 1101 |
| 60 | + value_type: U_WORD |
| 61 | + |
| 62 | + - platform: modbus_controller |
| 63 | + use_write_multiple: true |
| 64 | + modbus_controller_id: ${modbus_controller_id} |
| 65 | + id: battery_constant_voltage_mode |
| 66 | + name: "Battery constant voltage mode" |
| 67 | + min_value: 0 |
| 68 | + max_value: 1000 |
| 69 | + step: 0.1 |
| 70 | + unit_of_measurement: "V" |
| 71 | + multiply: 10 |
| 72 | + address: 1107 |
| 73 | + value_type: U_WORD |
| 74 | + |
| 75 | + - platform: modbus_controller |
| 76 | + use_write_multiple: true |
| 77 | + modbus_controller_id: ${modbus_controller_id} |
| 78 | + id: battery_constant_current_mode |
| 79 | + name: "Battery constant current mode" |
| 80 | + min_value: 0 |
| 81 | + max_value: 200 |
| 82 | + step: 0.1 |
| 83 | + unit_of_measurement: "A" |
| 84 | + multiply: 10 |
| 85 | + address: 1108 |
| 86 | + value_type: U_WORD |
| 87 | + |
| 88 | + - platform: modbus_controller |
| 89 | + use_write_multiple: true |
| 90 | + modbus_controller_id: ${modbus_controller_id} |
| 91 | + id: battery_constant_power_mode |
| 92 | + name: "Battery constant power mode" |
| 93 | + min_value: -120 |
| 94 | + max_value: 120 |
| 95 | + step: 0.1 |
| 96 | + unit_of_measurement: "%" |
| 97 | + multiply: 10 |
| 98 | + address: 1109 |
| 99 | + value_type: S_WORD |
| 100 | + |
| 101 | + - platform: modbus_controller |
| 102 | + use_write_multiple: true |
| 103 | + modbus_controller_id: ${modbus_controller_id} |
| 104 | + id: battery_constant_soc_mode |
| 105 | + name: "Battery constant SOC mode" |
| 106 | + min_value: 0 |
| 107 | + max_value: 100 |
| 108 | + step: 0.1 |
| 109 | + unit_of_measurement: "%" |
| 110 | + multiply: 10 |
| 111 | + address: 1110 |
| 112 | + value_type: U_WORD |
| 113 | + |
| 114 | + - platform: modbus_controller |
| 115 | + use_write_multiple: true |
| 116 | + modbus_controller_id: ${modbus_controller_id} |
| 117 | + id: inv_output_power_ABC |
| 118 | + name: "Inverter output power phase ABC" |
| 119 | + min_value: -120 |
| 120 | + max_value: 120 |
| 121 | + step: 0.1 |
| 122 | + unit_of_measurement: "%" |
| 123 | + multiply: 10 |
| 124 | + address: 1111 |
| 125 | + value_type: S_WORD |
| 126 | + |
| 127 | + - platform: modbus_controller |
| 128 | + use_write_multiple: true |
| 129 | + modbus_controller_id: ${modbus_controller_id} |
| 130 | + id: inv_output_power_A |
| 131 | + name: "Inverter output power phase A" |
| 132 | + min_value: -120 |
| 133 | + max_value: 120 |
| 134 | + step: 0.1 |
| 135 | + unit_of_measurement: "%" |
| 136 | + multiply: 10 |
| 137 | + address: 1112 |
| 138 | + value_type: S_WORD |
| 139 | + |
| 140 | + - platform: modbus_controller |
| 141 | + use_write_multiple: true |
| 142 | + modbus_controller_id: ${modbus_controller_id} |
| 143 | + id: inv_output_power_B |
| 144 | + name: "Inverter output power phase B" |
| 145 | + min_value: -120 |
| 146 | + max_value: 120 |
| 147 | + step: 0.1 |
| 148 | + unit_of_measurement: "%" |
| 149 | + multiply: 10 |
| 150 | + address: 1113 |
| 151 | + value_type: S_WORD |
| 152 | + |
| 153 | + - platform: modbus_controller |
| 154 | + use_write_multiple: true |
| 155 | + modbus_controller_id: ${modbus_controller_id} |
| 156 | + id: inv_output_power_C |
| 157 | + name: "Inverter output power phase C" |
| 158 | + min_value: -120 |
| 159 | + max_value: 120 |
| 160 | + step: 0.1 |
| 161 | + unit_of_measurement: "%" |
| 162 | + multiply: 10 |
| 163 | + address: 1114 |
| 164 | + value_type: S_WORD |
| 165 | + |
| 166 | + - platform: modbus_controller |
| 167 | + use_write_multiple: true |
| 168 | + modbus_controller_id: ${modbus_controller_id} |
| 169 | + id: remote_mode_max_solar_power |
| 170 | + name: "Remote Mode max solar power" |
| 171 | + min_value: 0 |
| 172 | + max_value: 200 |
| 173 | + step: 0.1 |
| 174 | + unit_of_measurement: "%" |
| 175 | + multiply: 10 |
| 176 | + address: 1115 |
| 177 | + value_type: U_WORD |
0 commit comments