Combined / Can be combined : This status indicates whether the BMS or Shunt is currently combined.
In this example there are 3x BMS and 1x BMS is not combined (it is offline or is not sending correct data).
Combine condition :
- the
Combineswitch is enabled - Shunt
Online StatusisON(the shuntVoltageis> 0)
If one of these two conditions is not respected, the shunt is automatically uncombined.
Important
In RS485 modbus multi-node, if a server does not respond (cable or hardware failure) the Online Status of the shunt will be set to OFF and it will be uncombined.
As soon as you import a Shunt and it can be combined (see condition) the values Voltage, Current, Power and SoC of the shunt(s) will take precedence over the BMS values.
Note
If all BMS are uncombined the shunt data will no longer be published.
If one shunt is used for multiple batteries, it is possible to provide the BMS IDs the shunt code with the variable bms_ids, example: bms_ids: '{1, 2, 3}'.
When the BMS IDs are provided to the shunt and one or more of the BMS are offline, the shunt Combine switch will be turned OFF.
This is helpful when one BMS/battery shuts down for a longer time. The SoC of the shunt will then not be correct anymore and this avoids that the batteries are
discharged further then wanted.
Note
You need to manually enable the Combine switch again if it was disabled automatically.
If you do not want that behaviour, do not provide bms_ids to the shunt.
Combine condition :
- BMS
Online StatusisON / Connected(to detect a loss of connection with the BMS e.g. cable, BMS OFF or dead) - The BMS
Battery Capacityis> 0(to ensure that the data received is correct)
If one of these two conditions is not met, the BMS is automatically uncombined.
Important
In RS485 modbus multi-node, if a server does not respond (cable or hardware failure) the Online Status of the BMS will be set to OFF and it will be uncombined.
From YamBMS 1.5.1 :
The binary_sensor does not only represent the state of the charge/discharge switches but simply whether the charge/discharge is allowed. The value of binary_sensor is related to the status of the switches/alarms.
The errors_bitmask should not be a condition to combine a BMS anymore, let the BMS decide if the charge/discharge is allowed (its alarm system takes care of that).
The errors_bitmask continues to be analyzed to send warnings/alarms to the inverter.
The behavior of the Charging Instruction and Discharging Instruction sensors responsible for the instructions sent to the inverter will also be adapted. Alarm analysis will no longer be checked. If at least one BMS allows charging, charging can continue, if at least one BMS allows discharging, discharging can continue. This will also be based on the binary_sensor related to the state of switchs/alarms of the BMS.
If a BMS blocks charging or discharging, the permitted current is automatically reduced.
If an external balancer is used instead of the BMS internal one, it can be combined with the BMS.
Behaviour for equalizing and balance trigger voltage:
- When no external balancer is present for a BMS or it is offline, the BMS values are used for
equalizingandbalance trigger voltage. - When an external balancer is present for a BMS and it is online, the BMS sensor data for
equalizingandbalance trigger voltageis overwritten by the external balancer sensor data.
The SoC is slightly manipulated before reaching 0% or 100%.
SoC 100% will be sent to your inverter only when the battery is fully charged (useful for some inverters stopping charging when the SoC reaches 100%).
SoC behavior:
- If
SOC < 99%real SoC is sent - Else if
the battery is fully chargedreal SoC is sent - Else SoC
98%is sent
The system uses Synchronized Diagnostic Blink Codes. This allows the device to communicate specific fault categories visually without requiring a network connection.
If no faults are present, the LED indicates the system is alive.
-
Pattern: 🟢 Green Pulse (1s)
$\rightarrow$ ⚫ OFF (1s). - Meaning: All linked components operational.
- Cycle Time: ~2.0 Seconds.
When a fault occurs, the cycle changes to a strict 3-part message structure.
| Phase | Color | Duration | Description |
|---|---|---|---|
| 1. Header | 🔵 Blue | 1.0s | "Attention." Marks the start of a error report cycle. |
| 2. Gap | ⚫ OFF | 0.5s | "Wait." A short pause to prepare for counting. |
| 3. Code | 🔴 Red | Variable | "Data." A set count of short Red blinks. |
The number of Red blinks corresponds to the Fault Category (see table below). To make counting easier, long codes are broken into groups of 4:
- 5 Pips:
* * * *...* - 9 Pips:
* * * *...* * * *...*
| Blinks | Category | Description |
|---|---|---|
| 1 | API / MQTT | API or MQTT communication failure. |
| 2 | BMS | Battery Management System communication failure. |
| 3 | INV CAN | Inverter CAN bus communication failure. |
| 4 | INV RS485 | Inverter RS485 bus communication failure. |
| 5 | SHUNT | Shunt communication failure. |
| 6 | BALANCER | Balancer communication failure. |
| 7 | NETWORK | No wifi or ethernet connection. |
| 8-16 | AUX 1-9 | Reserved for future expansion. |
When a fault is active anywhere in the system:
- Fault LEDs: Display the Red error code.
- Healthy LEDs: Turn OFF during the "Code" phase This reduces visual noise, highlighting exactly which components requires attention.
If a single LED monitors multiple components (e.g., a LED monitoring both the BMS and the Shunt) and both fail simultaneously:
- Cycle 1: Displays BMS Code (2 Pips).
- Cycle 2: Displays Shunt Code (5 Pips).
- Repeat: The LED rotates through active faults one by one.
For boards without RGB LEDs:
- Header: Solid on.
- Code: Blinking.
- Gap/Healthy: off.
For boards with multiple LEDs, it's possible to assign a specific led to a specific component. For example, led_1 for BMS 1, led_2 for canbus. See the section below for more details.
The system links specific hardware LEDs to software components using Substitutions in your YAML package configuration.
Each component package (BMS, canbus, etc.) includes a specific variable to define which LED should report its status.
In your main YAML file, under packages, you assign the Light ID to the *_status_led_id variable.
In most cases, the default values can be used but some boards such as the LilyGo T-Connect have multi-LED functionality.
- path: 'packages/bms/bms_combine_JK_RS485_Modbus_bms_standard.yaml'
vars:
# Unique ID for this specific instance
bms_id: '1' # must be a number
bms_name: 'JK-BMS 1'
bms_address: '0x01' # BMS 1 DIP switch
# LINKING THE LED
# Set this to the ID of the light component defined in your ESPHome config.
# Example: 'esp_light', 'led_1', etc. The board config will show further details
bms_status_led_id: 'esp_light' # LED used to show status; default = esp_light, comment out to disableFor the CAN bus link to be established with your inverter, the three conditions below must be met:
- At least
oneBMS iscombined - The YamBMS status must be
initialized - Your inverter sends an
ACK 0x305every1s(the link will be faulty if no ACK is received for5s)
If these conditions are not met, the application waits 30s before trying to connect again.
During boot or when switching from 0 to 1 combined BMS, the CAN bus starts after YamBMS initialization, which can take 30s...
Sending CAN frames continues without an inverter connected is problematic and will lead to ESP32 crash.
For this reason, if the inverter does not respond after 5s, the link is paused for 30s before attempting to re-establish the communication.
The Deye inverter sends the ACK (can_id 0x305) only when it receives the can_id 0x356.
- path: 'packages/yambms/yambms_canbus.yaml' # yambms_canbus_web_server.yaml
vars:
canbus_id: '1' # must be a number
canbus_name: 'CANBUS 1'
canbus_node_id: 'canbus_inverter_1' # CAN bus node to which your inverter is connected
canbus_status_led_id: 'esp_light' # LED used to show status; default = esp_light, comment out to disable
# The CAN bus link will be paused for `30s` if the inverter does not respond with an ACK (can_id 0x305)
# before the end of the `canbus_link_timer` (5s by default).
canbus_link_timer: '5s'
canbus_extended_ack: 'false' # Set to 'true' for enable extended 29-bit IDs for the ACK can_id 0x305 (required for Schneider XW Pro)If all BMS have alarms, the alarms are sent to the CAN bus as Protection Alarms.
If at least one BMS has no alarms, the alarms are sent to the CAN bus as Warning.
Both text_sensor Alarm and Warning show the alarms/warnings currently transmitted to the inverter.
Each BMS transmits its alarms using the YamBMS errors_bitmask in the format below :
# +--------------------------------------+
# | YamBMS Errors Bitmask (16bit) |
# +--------------------------------------+
# Bit 0 General alarm 0000 0000 0000 0001 0x0001
# Bit 1 Battery high voltage alarm 0000 0000 0000 0010 0x0002
# Bit 2 Battery low voltage alarm 0000 0000 0000 0100 0x0004
# Bit 3 Battery high temperature alarm 0000 0000 0000 1000 0x0008
# Bit 4 Battery low temperature alarm 0000 0000 0001 0000 0x0010
# Bit 5 Battery high temperature charge alarm 0000 0000 0010 0000 0x0020
# Bit 6 Battery low temperature charge alarm 0000 0000 0100 0000 0x0040
# Bit 7 Battery high discharge current alarm 0000 0000 1000 0000 0x0080
# Bit 8 Battery high charge current alarm 0000 0001 0000 0000 0x0100
# Bit 9 Contactor alarm 0000 0010 0000 0000 0x0200
# Bit 10 Short circuit alarm 0000 0100 0000 0000 0x0400
# Bit 11 BMS internal alarm 0000 1000 0000 0000 0x0800
# Bit 12 Cell imbalance alarm 0001 0000 0000 0000 0x1000
# Bit 13 Reserved 0010 0000 0000 0000 0x2000
# Bit 14 Reserved 0100 0000 0000 0000 0x4000
# Bit 15 Reserved 1000 0000 0000 0000 0x8000