Sungrow SH residential hybrid — Modbus RTU register map

Single-phase hybrid with a battery port. The profile lives in profiles/sungrow/sh_hybrid.toml.

STATUS: Experimental — but the best-sourced map in this tree. The rows come from Sungrow's own protocol specification, cross-checked register by register against a widely deployed implementation. Not yet confirmed against a physical inverter by this project.

Connection

Port RS485 on the inverter's own COM terminal (A1/B1); no WiNet dongle required
Line 9600 8N1, RTU
Register space Input registers (function 04) for readings; holding (03) for setpoints

The vendor document states this directly: communication runs over the RS485 interface on the inverter or the Ethernet interface of a WiNet-S/Logger, so a direct RS485 connection is a first-class path rather than a workaround.

Sources

What
A Sungrow, Communication Protocol of Residential Hybrid Inverter V1.1.9 (PDF) — a vendor specification, the top of the trust order in adding-a-device.md
B mkaiser/Sungrow-SHx-Inverter-Modbus-Home-Assistant, modbus_sungrow.yaml

Source B is unusually useful for cross-checking because every entry carries both the protocol address and the document's own register number in a comment (address: 5016 # reg 5017) — which turns the comparison into something mechanical rather than a judgement call.

A note on reading the PDF

No PDF tooling was available, so the document was decompressed and its text operators extracted directly. That worked for the register tables — addresses, data types and units come out plainly — but the document mixes fonts, and some name columns are in a subset font whose glyph codes did not survive extraction. Where that happened, the row is identified in this profile by its address, type and unit from the document, with the name taken from source B. That split is called out per row in the profile comments; it is not a detail to paper over.

Two traps, and both apply to every row

The numbering trap

The vendor document numbers registers from 1. Modbus addresses them from 0.

PDU address = document register number − 1

The document's "Total DC power 5017~5018" is PDU 5016. Source B writes exactly that, and the relationship was verified mechanically across all 88 of its addressed entries: the offset is 1 in every single one, no exceptions, in both the 5000 and 13000 ranges.

Every address in the profile is a PDU address. Off by one here reads a neighbouring register that is usually also a plausible number — the kind of wrong that survives a casual bench check.

The word-order trap

This family stores every double-word value LOW WORD FIRST. Source B declares swap: word on all 21 of its 32-bit sensors — checked mechanically, no exceptions — and the vendor document says the same in its type definitions.

So every u32/s32 row in the profile carries word_order = "low_first". An earlier version of this document and the profile had it on the battery-power row alone, with a comment claiming that row was "the opposite of every other 32-bit value in this map". That was false, and it cost six rows a factor of 65536 each — 4 kW of PV would have published as about 262 megawatts.

It was caught in review by checking the source mechanically instead of believing the comment, and the profile now has a test asserting the convention per family rather than per row. The frame-decoding test did not catch it: that test was written from the profile, so it agreed with the mistake.

Mapped registers

PDU addresses, all input registers. value = raw × scale.

PDU Doc Type Scale Canonical id
5007 5008 s16 0.1 inverter.temperature
5010 5011 u16 0.1 dc.mppt_1.voltage
5011 5012 u16 0.1 dc.mppt_1.current
5012 5013 u16 0.1 dc.mppt_2.voltage
5013 5014 u16 0.1 dc.mppt_2.current
5016 5017 u32 1 dc.power.total
5018 5019 u16 0.1 ac.phase_l1.voltage
5213 5214 s32, low-word-first, scale −1 battery.power — see below
5241 5242 u16 0.01 ac.frequency
13001 13002 u16 0.1 energy.today
13002 13003 u32 0.1 energy.total
13019 13020 u16 0.1 battery.voltage
13022 13023 u16 0.1 battery.soc — tenths of a percent
13024 13025 s16 0.1 battery.temperature
13026 13027 u32 0.1 battery.energy_discharged
13030 13031 s16 0.1 ac.phase_l1.current
13033 13034 s32 1 ac.power.total
13040 13041 u32 0.1 battery.energy_charged

Three of these are worth stating explicitly, because each is a mistake waiting to happen:

Battery SoC is in tenths of a percent. Both sources say so. Read as whole percent, a full battery publishes as 1000%.

Two frequency registers exist, both in the document: 5036 at 0.1 Hz and 5242 at 0.01 Hz. The finer one is mapped. 0.1 Hz is too coarse to see the grid excursions this channel is worth watching for.

Energy comes from the hybrid block, not the common block. The 5003/5004 pair is named "PV generation & battery discharge" by both sources — it includes energy that came back out of the battery, so feeding it to an energy dashboard counts stored solar twice. 13002/13003 is PV generation alone.

Battery power: the register that needed two new schema features

This is the first battery.power row in the tree that could be mapped at all. The Deye map leaves it out because neither source states the direction; the Solis map leaves it out because the direction lives in a separate register. Sungrow states everything — and then needs two corrections at once.

Source B records the vendor's own guidance alongside the register:

In datasheet (1.1.11) it is recommended to use this register instead of 13022 negative: Battery charging positive: Battery discharging

The document's own table confirms the shape — row 31, registers 5214-5215, S32, 1W — while the row's name is in the subset font that did not extract. So: the document supplies the address, width and unit; source B supplies the name and the sign convention, and the fact that the datasheet steers you here rather than to the unsigned alternative at 13022.

Two things follow:

  1. word_order = "low_first". Source B reads this pair with swap: word — the low half sits at the lower address. Read the default way round, 2 kW decodes as roughly 34 megawatts.
  2. scale = -1. Our canonical convention is positive while charging (the SunSpec storage convention). This device states the opposite, so the sign is flipped in the profile rather than in C++.

Both are corrections a source states. That is exactly the line the other two hybrid profiles could not cross.

Low-word-first support was added to the profile schema for this register. It was previously documented as "open an issue rather than mapping it wrong", which in practice meant declining to read the register the manufacturer points you at.

Not mapped

  • Export power (13010). Both sources agree. (Load power was in this list until load.power joined the vocabulary; PDU 13007 is mapped now and appears in the table above.) Export power is signed and bidirectional; our grid channels are two unsigned rails, so splitting it needs arithmetic a profile cannot do.
  • Imported/exported energy (13036/13037, 13045/13046). Agreed, but our grid.* channels are instantaneous power rather than energy.
  • MPPT 3 (5014/5015) and MPPT 4 (5114/5115). Real on the larger models and present in both sources; mppts = 2 describes what this profile maps. A three-tracker unit shows its third string in the raw dump and gains two rows once somebody confirms the model.
  • The alternative battery power at 13021. Unsigned, and the register the datasheet steers away from.

Writing

Both setpoints are corroborated by both sources — better standing than the single-sourced write rows in the Deye and Solis profiles — and both stay dormant until somebody confirms them on hardware.

PDU Doc Command Notes
13073 13074 set_export_limit_watts u16, watts, step 10
13049 13050 set_battery_operating_mode 0 Self-consumption, 2 Forced, 3 External EMS, 4 VPP

The export limit has an enable switch. On this family the limit is governed by a separate mode register (13086 in source B's numbering). Writing a limit while that switch is off changes a stored number and nothing else — which on a bench looks exactly like a write that did not work. Check the mode register first.

Mode 1 is deliberately absent from the options list: neither source lists it, and filling the gap by assuming the numbering is contiguous is the guess that puts a hybrid in an untested state.

Bring-up checklist

  • Wire A/B to the inverter's RS485 terminal.
  • Select driver modbus_profile, profile sungrow_sh_hybrid.
  • Set log level trace; confirm all three blocks answer.
  • Check each mapped row against the inverter's own display at that moment.
  • Watch battery power through a charge→discharge crossover. It should read positive while charging. If it reads negative, the scale = -1 is wrong for this firmware; if it reads in the tens of megawatts, the word order is.
  • Report back either way.