MQTT connections

Purpose

Set up and check MQTT in the Admin Console: a local broker, the Zendure cloud broker, several brokers side by side, MQTT grid meters, and the gates that decide whether EMS may actually write.

This page is the Admin Console workflow. For what each transport is, how fast it is and which hardware suits it, read Connection types — that page owns the transport semantics and the measured latency figures.

When to use this workflow

  • Your inverter has no usable local API.
  • You already run a local broker and want telemetry to stay on your network.
  • You want to try the software with any Zendure device via the cloud.
  • You want to check why an MQTT device is telemetry-only.

Prerequisites

For Local MQTT:

  • A broker (for example Mosquitto) reachable from the EMS host.
  • The device already publishes to that broker. Zendure hardware normally talks to Zendure's cloud broker, so you must re-point it yourself first. EMS does not automatically redirect a device's MQTT configuration.
  • Credentials and TLS settings for the broker, if it needs them.

For Zendure Cloud MQTT:

  • Your Zendure API key.
  • Working internet access.
  • No other controller regulating the same device.

Local MQTT

1 — Add the broker

Where: Maintenance → Settings & devicesHardwareLocal MQTT broker (optional). In Guided Setup the same form is under Add a device manually.

What you enter: host, port, credentials and TLS settings.

What it changes: the draft. Nothing connects until you apply.

Expected result: the broker appears as a configured profile that devices can be assigned to.

2 — Assign devices to the broker

What you see: each MQTT device carries a broker reference, so a device knows which broker it belongs to.

What it changes: which broker EMS subscribes to for that device.

If it differs: if the device is not actually publishing to that broker, EMS will show it as unseen or stale. Re-point the device first — see Connection types → Local MQTT for community projects that help with re-pointing and topic decoding.

3 — Check the result

Device telemetry card showing a local broker and the cloud broker, both connected, with two online devices

Where: Maintenance → Device telemetry.

What you see: runtime state, endpoint, device count, invalid devices, stale threshold, a card per broker (source, endpoint, device count, connection status) and a card per device (broker, source, topic family, age, metric count, capabilities).

What it changes: nothing. This panel is read-only and does not send commands. Configured MQTT control devices may still be controlled by the EMS runtime — that is the runtime's job.

Expected result: brokers connected, devices online, a low age, and capabilities listing what the device can do.

If it differs: Unavailable means EMS could not report live status. Devices with 0 metrics or a large age are not publishing what EMS expects.

Zendure Cloud MQTT

1 — Store the API key

What you enter: your Zendure API key in the Admin Console.

What it changes: the key is stored encrypted in the external secret store. It is never shown back to you.

2 — Authorize and list devices

What it changes: the console logs in to Zendure's device-list service with your key and lists your devices. This is a read step.

Expected result: your Zendure devices appear as selectable cloud connections.

3 — Apply a selected cloud device

What it changes: this is where the credential is provisioned. The Apply step fetches fresh broker credentials with your API key, stores them encrypted in the external secret store, and verifies that EMS can resolve them before the config is committed.

Expected result: the broker connects over TLS and telemetry arrives.

If it differs: if that credential record is later missing, the broker reports broker_auth_missing and is never connected — it fails closed rather than retrying blind.

What to expect from the cloud path

  • Internet dependency. No connectivity, no cloud telemetry and no cloud writes.
  • Higher latency than Local API or Local MQTT. See the measured figures in Connection types. Use system.loop_interval = 5 seconds with Zendure Cloud MQTT.
  • A published command is not a successful command. EMS reports a command effective only after telemetry confirmation; publishing is only a transport step. See Dashboard control.
  • Run only one controller. Disable Zendure HEMS, Smart Matching and Zendure schedules when EMS controls a device over the cloud broker.

The cloud broker is bidirectional only with the Zendure App / Home Assistant authorization credentials returned by the device-list login. The public read-only developer MQTT account can subscribe to telemetry, but its writes are silently discarded.

Multiple brokers, and mixed operation

You can run several brokers at once, and mix transports freely:

  • Each MQTT device carries an explicit broker reference, so two brokers never compete for the same device.
  • One inverter on Local API and another on Zendure MQTT is a supported, normal setup. They join the same EMS control loop.
  • A single physical inverter reachable over several transports stays one logical device. See Device management.

MQTT grid meters

A Zendure D0 discovered on a local MQTT broker offers "Use as grid meter". Choosing it maps the D0's Zendure/sensor/<serial>/totalPower topic to the central grid meter, reusing the selected broker profile.

Only one grid meter can be active, and an existing one is replaced only when you explicitly confirm it. A Zendure D0 or Smart Meter 3CT found over local HTTP is the simpler choice when you have it — no MQTT setup at all.

Write safety gates

Whether EMS may write to hardware is decided by named gates, one per transport. All three default to on, and each can be switched off for read-only validation.

Transport Gate
Local API / local HTTP allow_hardware_writes
Local MQTT broker allow_mqtt_local_control_writes
Zendure cloud MQTT allow_mqtt_zendure_control_writes

Every runtime write additionally requires dry_run=false, simulation_mode=false and not being a replay.

A gate being on is not enough on its own. Output control over MQTT needs the whole chain:

  • an exact supported hardware model, resolved from verified device evidence;
  • a compatible broker transport for that model;
  • a verified write protocol for it;
  • an enabled control capability (the per-device write_output_limit opt-in);
  • an enabled transport write gate.

Topic family and generation are evidence and telemetry grouping only — they never authorize a write. Unknown or conflicting model evidence keeps a device telemetry-only.

Broker source is part of the decision: a ZenSDK/scalar local generation entered through the manual local broker form stays telemetry-only with the reason "Output control is not verified for this MQTT broker source", while the Zendure cloud broker keeps control for a supported model.

Full model: Safety · Safety model (technical).

State reconciliation is still API-only

MQTT does not yet replace every Local API function. State-reconciliation writes — minSoc, socSet, smartMode, gridOffMode, winter inputLimit, full-charge assist — additionally require allow_state_reconciliation_writes=true and are API-only. MQTT control devices are output-only.

If you need those features, keep at least one API path to the device.

Zendure MQTT migration during an upgrade

A Guided Upgrade reviews the Zendure MQTT migration before it applies anything, and names:

  • which devices the migration affects, and
  • which devices would lose control.

Read that list before confirming. The review is read-only; the migration is applied through the EMS-owned migration service, in the upgrade's own ordered pipeline. Maintenance also exposes the review on its own card.

Limitations, honestly

  • Cloud confirmation is delayed. Measured on a physical SolarFlow 800 Pro 2: 165 of 165 commands confirmed, typically ~2.9 s, slowest 3.4 s. Measured values, not a guarantee.
  • Some legacy generations are partly reverse-engineered. The legacy Zendure JSON write method is validated in the test harness; the older non-modern-API generations (Hub / Hyper / AIO / Ace) have not been confirmed on real hardware.
  • Not every model is validated on physical hardware. See Supported setups for the four support tiers and the evidence behind each row.
  • Unknown or conflicting models stay telemetry-only by design.

Positive reports are just as valuable as problem reports — they let a device be marked validated for everyone. Open a Device compatibility report with model, firmware, connection type and sanitized logs. Remove serial numbers, tokens, passwords and public IPs first.

Warnings and common problems

Symptom Meaning What to do
Broker card shows disabled / not connected Profile disabled or unreachable Check host, port, credentials, TLS
broker_auth_missing The encrypted credential record is gone Re-apply the cloud device to re-provision it
Device unseen or large age It is not publishing to that broker Re-point the device; EMS never redirects it for you
Device is telemetry-only The authorization chain is incomplete Why a device is read-only
Not ready naming a missing identifier Product key or MQTT device ID missing Complete the write route
Control seems slow over cloud Expected Use a 5 s loop interval; prefer a local transport
Values fight back / oscillate A second controller is active Disable Zendure HEMS, Smart Matching and schedules

Recovery or next steps