HeishaMon rules with an OpenTherm thermostat

These are the rules I use to control a Panasonic heat pump with an OpenTherm thermostat. They are tailored to my installation; use them as inspiration and adapt the settings and integration to your own system.

Current version: 2610.06

See CHANGELOG.md for the changes in each published version.

File Purpose
HeishaMon_Rules_BlB4.lua Ready-to-load rules without comments
HeishaMon_Rules_BlB4_commented.lua Readable source with explanations; minify before loading

The .lua extension is a filename convention: these files use the HeishaMon rules language, including on ... then, @, #, $ and ? variables. They are not standard Lua programs.

My setup

  • Panasonic WH-MDC07J3E5 for heating, cooling and domestic hot water with an external tank; radiators and convectors.
  • HeishaMon Large. The supplied source identifies firmware builds Alpha-f7ae839/Alpha-d8af83f in the 4.0 development series. Use firmware that supports this ruleset's size, OpenTherm integration and coalesce() function; compatibility with other builds has not been verified here.
  • CZ-TAW1 connected to the proxy port; I do not use it actively.
  • Honeywell Evohome with an R8810 OpenTherm bridge, connected through an OpenTherm Gateway.
  • Home Assistant with Evohome and OpenTherm Gateway integrations. Home Assistant supplies the living-room target and current temperature through the OTGW as normal OpenTherm room values, because Evohome's chSetpoint is not suitable as the primary control input for this heat-pump strategy.
  • OTGW firmware 6.7 or newer is required for the RT= command used to provide Room Temperature (OpenTherm Data-ID 24).
  • Heat-pump settings: Heating_Mode: 1 (direct), Cooling_Mode: 1 (direct), Buffer_Installed: 0, DHW_Installed: 1, Pump_Flowrate_Mode: 0, Optional_PCB: 0, Z1_Sensor_Settings: 0.

What the rules do

  1. Adjust maximum pump duty for heating, cooling, DHW and idle operation.
  2. Set Quiet Mode based on compressor frequency, runtime, outside temperature, time of day and operating mode; allow an override through the buffer-tank delta setting.
  3. Schedule DHW and sterilisation runs, with additional tank-temperature triggers and restoration of the previous operating mode/state.
  4. Synchronise heat-pump temperatures and operating status with OpenTherm.
  5. Control heating demand using filtered chEnable, room-temperature difference, outside temperature and runtime conditions.
  6. Calculate weather compensation and use TaShift with room-temperature PID correction to adjust the heating target and support longer compressor runs.
  7. Control cooling using Home Assistant/OpenTherm enable and water-temperature requests.
  8. Handle the weekly clock rollover in compressor and thermostat elapsed-time calculations.

OpenTherm room values

The room setpoint and current room temperature are transported as their normal OpenTherm values instead of encoding room temperature in maxRelativeModulation.

  • ?roomTempSet is the room setpoint (OpenTherm Data-ID 16). In this setup Home Assistant writes the living-room target temperature to the OTGW with BS=<temperature>. The rules limit the resulting setpoint to 10–22 °C.
  • ?roomTemp is the current room temperature (OpenTherm Data-ID 24). Home Assistant writes the living-room current temperature to the OTGW with RT=<temperature>. The RT= command requires OTGW firmware 6.7 or newer.
  • If the thermostat does not itself provide Data-ID 24, the OTGW can be configured to provide it as an alternative Data-ID (AA=24).
  • ?chEnable remains the heating-demand signal from Evohome; short off periods are filtered by the rules with a delay greater than 15 minutes.

The old use of ?maxRelativeModulation as an encoded room-temperature transport is no longer used.

Filtering the room temperature upstream

In this installation the Evohome/ramses room-temperature value occasionally shows short, non-physical spikes or dips. Because ?roomTemp is used directly by TaShift and the thermostat logic, such glitches can otherwise cause a short target-temperature jump.

Home Assistant therefore filters the raw living-room temperature before sending it to the OTGW with RT=. The current setup uses a Home Assistant filter sensor with a lowpass filter, time_constant: 15 and precision: 2, and the OTGW automation rounds the filtered result to 0.1 °C before sending it. This filtering is installation-specific and is not part of the HeishaMon rules themselves.

HEMS GPIO heat-demand block (2610.05)

Timer 8 reads gpio(33). Only an explicit value of 1 forces the internal filtered #chEnable to zero; otherwise normal Evohome ?chEnable processing applies. This affects the filtered demand input, while actual heat-pump stop conditions are still evaluated by timer 4.

Startup behaviour

When the rules are loaded while the compressor is already running, timer 1 marks it with #CompState = 2. Version 2610.06 retains the existing TaShift target-write logic; a proposed additional guard to prevent a transient downward target write during a running-compressor reload is not included in these uploaded files.

Other integration values to check

  • ?dhwEnable enables the rules' DHW control.
  • ?CoolingEnable enables cooling and is smoothed by the rules. Home Assistant supplies ?coolingControl from its dew-point calculation; the rules apply further water-temperature limits. Configure this external calculation for your installation.
  • @Z2_Heat_Request_Temp provides a heating-target override: 15–25 corresponds to a −5 to +5 °C shift around 20; values above 25 request a direct temperature.
  • @Buffer_Tank_Delta below 4 overrides Quiet Mode.
  • Review the DHW settings, hardcoded comfort-day condition (%day == 4), #DHWSterilizationDay, weather-curve settings, hardcoded upper curve temperature (36 °C) and pump settings before use. The #DHWComfortDay variable is initialised but the trigger currently uses the hardcoded day.

Loading and editing

  1. Save a copy of your existing rules and check the settings and integration above.
  2. Load the contents of HeishaMon_Rules_BlB4.lua into the HeishaMon rules editor, without Markdown fences.
  3. Check the boot log for BLB Heishamon_rules_2610.06.lua and monitor operation in your installation.
  4. Verify that ?roomTempSet and ?roomTemp contain the intended living-room target and current temperature before relying on room-temperature correction.

For edits, work in HeishaMon_Rules_BlB4_commented.lua, then generate the ready-to-load file using the HeishaMon rules minifier. Keep both files in sync.

Usage is at your own risk. These are personal control rules, including installation-specific heating, cooling and hot-water settings.

Thanks to HeishaMon, @CurlyMoo for the rules functionality and @fbloemhof for the documentation inspiration.

Licensed under the MIT License.