An unofficial, experimental Python controller for Mitsubishi mini-split heat pumps on Kumo Cloud and the Mitsubishi Comfort app. Instead of Auto mode's heat/cool changeover, it keeps the unit in heat, steers the setpoint toward 70°F from a 15-minute temperature prediction, and cools only when sun pushes the room to 73°F or more (as low as 71.5°F on cold days when outdoor data is configured).
Status: experimental. It runs daily in the author's home but has not yet proven steadier than a simpler approach there. Treat it as a starting point and check your own log.
In the author's own trial, this version has not yet beaten an earlier, simpler version (roughly 44% vs 71% of time in band). Strong afternoon sun also pushed the room above the band.
It talks to the same cloud backend as the Mitsubishi Comfort app (Kumo Cloud v3) through a bundled client, runs every 10 minutes on any always-on machine with Python 3.11+, and writes a CSV log so you can check your own results. Not affiliated with Mitsubishi Electric.
Mitsubishi's Auto mode keeps a heat setpoint and a cool setpoint and only changes mode when the room crosses the other one. A 67/73 Auto (the defaults scripts/restore.sh puts back) is not trying to hold a 69 to 71°F band at all: in the same simulation it spends 73% of the day below 69°F. A fair comparison sets Auto to 70/72, aimed at the band, and that is what Chart 1 shows. In that simulation both hold the band about equally (75% for Stock Auto, 77% for the controller); the difference is cooling. Stock Auto switches to cooling as soon as afternoon sun takes the room past 72°F and cools for 4.2 hours, while the controller stays in heat until the room holds 73°F and cools for 2.7 hours. The trade-off is a warmer afternoon: the controller peaks near 73.7°F against about 72.9°F for Stock Auto.
The controller stays in heat and steers the heat setpoint between 66 and 71°F from a predicted room temperature 15 minutes ahead (Tp = current temp + 0.25 h × slope). It lowers the setpoint right away when Tp says the room is heading up, and raises it at most 1°F per 15 minutes. Every 3 hours it compares the time-weighted mean with the 70°F target and trims the whole table by 1°F if the mean drifted more than 0.4°F. It only cools when the room holds at or above 73°F for 20 minutes, which in practice means solar gain. With a fresh outdoor reading (at most 2 hours old) that entry point drops to the cool target + 1.5°F when that is lower. In cool, the room target follows outdoor temperature: 70.0°F when it is 55°F or colder outside, rising linearly to 73.5°F at 80°F or warmer (72.0°F without outdoor data). The cool setpoint comes from a formula: u = target + cool trim − 1.5 × (Tp − target), kept between a floor of target − 1.5 rounded up and 78, and rounded to the nearest degree. It only changes when u is at least 0.75°F away from the current setpoint; raises happen at once, drops at most once per 15 minutes, by 2°F when Tp is more than 1.5°F over the target. A slow cool-only trim (−2 to 0) corrects a room that keeps settling above the target. The fan is staged from how far the room is from where it should be (quiet up to superPowerful) instead of sitting on auto.
It runs every 10 minutes, sends only the settings that differ from the unit's live state, never touches the vane, never turns a switched-off unit back on, and writes one row per cycle to a CSV log.
flowchart TD
A["Every 10 min"] --> B{"Backoff / read error / offline / off?"}
B -- yes --> Z["Log, change nothing"]
B -- no --> C["T, g, slope S, Tp = T + 0.25×S"]
C --> O["Outdoor ≤ 2 h old?<br>yes: cool target 70.0 to 73.5 from outdoor<br>no: cool target 72.0, h2c = 73"]
O --> D{"g ≤ 30?"}
D -- no --> H
D -- yes --> E{"Regime?"}
E -- heat --> F{"Held ≥ h2c for 20 min (1 h dwell)<br>or outdoor ≥ 62 and room ≥ h2c (3 h dwell)?<br>h2c = min(73, cool target + 1.5)"}
E -- cool --> G{"Held ≤ 68 for 45 min (3 h dwell)?"}
F -- yes --> FC["Switch to cool"]
G -- yes --> GH["Switch to heat"]
F -- no --> H
G -- no --> H
FC --> H
GH --> H
H{"Regime"} -- heat --> HH["Heat SP 66 to 71 from Tp table + trim<br>lower now, raise slowly"]
H -- cool --> CA["u = target + cool trim − 1.5×(Tp − target)<br>kept within ceil(target − 1.5) to 78<br>cool SP = u rounded, changed only when 0.75 away<br>raise now, drop 1 or 2 per 15 min"]
HH --> S["Stage fan from error, send only differences, log"]
CA --> S
T is the wireless sensor reading if it is at most 20 minutes old, else the unit's own reading. g is the number of minutes since the last good reading; after a gap longer than 30 minutes the controller still follows T but skips the slope, regime switches and trim.
Charts are a simulation that shows the behavior. Your results depend on your room, unit and climate.
The simulation (scripts/simulate.py) runs a simple one-room thermal model for 24 hours under the same outdoor temperature and sun curves twice. Both runs use the same modulating indoor unit (a PI loop with a minimum output that cycles off past its setpoint): once with Stock Auto at 70/72°F and its own changeover, and once driven by this controller's real decision code. Chart 3 adds a 67/73 Auto run for reference; it is not aimed at the band. The afternoon sun is calibrated to the 74.3°F afternoon peak in the author's real log, recorded under an earlier cool design; with the current cool formula the simulated peak is about 73.7°F. The simulated controller gets no outdoor reading, so it runs on the 72.0°F fallback cool target (floor 71) and the 73°F entry point, exactly as an install without MSC_LATITUDE / MSC_LONGITUDE would. The dynamics use no random numbers; the seed (42) only adds display noise, so python scripts/make_charts.py redraws identical charts every time.
Overnight the controller toggles its heat setpoint between 69 and 70°F about every 30 minutes, because the predicted temperature sits right on a table threshold. The unit only sees a 1°F nudge each time, so the room stays steady.
You need a Mitsubishi Comfort app account with the unit already set up in the app, and Python 3.11 or newer. Run these from the repository root: the default MSC_CLIENT_CMD is python3 client/mitsubishi.py, a relative path.
git clone https://github.com/chrisperish/mitsubishi-mini-split-controller.git
cd mitsubishi-mini-split-controller
python3 -m venv .venv && . .venv/bin/activate
pip install -e .
minisplit-controller --help
export MITSUBISHI_COMFORT_EMAIL="you@example.com"
export MITSUBISHI_COMFORT_PASSWORD="..."
python3 client/mitsubishi.py login # store cloud tokens
python3 client/mitsubishi.py status # find your unit's serial or name
export MSC_DEVICE="Living Room" # your unit's serial or name
minisplit-controller --once --dry-run # decide and print, change nothingWithout MSC_DEVICE the controller stops at startup with a message asking for it. When the dry run looks right, see Run and schedule. scripts/restore.sh puts the unit back on stock Auto 67/73.
To try it with no unit at all, run the simulation that draws the README charts: pip install -e ".[charts]" && python scripts/make_charts.py.
| Item | Status |
|---|---|
| Cloud / API | Mitsubishi Comfort app cloud (Kumo Cloud v3, app-prod.kumocloud.com). This is the only path the controller uses |
| Kumo Cloud Wi-Fi adapter units set up in the Comfort app | Expected to work; tested on one unit |
| MELCloud (Mitsubishi Electric outside North America) | Not supported: different cloud, not implemented |
| Local LAN control | Not used by the controller. The bundled client has an experimental --transport lan option, untested with the controller |
| Specific indoor unit models | Unknown: no model list has been verified |
| Multiple indoor units | One unit per controller instance (MSC_DEVICE); running several instances is untested |
| Mitsubishi wireless temperature sensor | Supported, optional |
| Units of °C | The controller logic works in °F; °C-only accounts are unknown |
| Python | 3.11 or newer (requires-python); tests run on Linux |
| Operating system | Linux verified; macOS likely (POSIX scripts, fcntl); Windows unknown and unlikely (fcntl is POSIX-only) |
| Home Assistant | Not an integration; runs as a standalone process |
- A Mitsubishi mini-split on a Kumo Cloud / Mitsubishi Comfort Wi-Fi adapter, set up in the Mitsubishi Comfort app.
- Recommended: a Mitsubishi wireless temperature sensor paired to the unit and placed where you sit. The controller uses the sensor when its reading is at most 20 minutes old and falls back to the unit otherwise.
- Any always-on machine with Python 3.11 or newer and internet access.
Install first (Python 3.11+). The [charts] extra adds matplotlib for scripts/make_charts.py; [dev] adds pytest too:
pip install -e . # controller and the bundled Comfort client
pip install -e ".[charts]" # optional: regenerate the charts
pip install -c constraints.txt -e ".[dev]" # exact versions used for the tests and committed chartsCredentials only ever come from environment variables:
export MITSUBISHI_COMFORT_EMAIL="you@example.com"
export MITSUBISHI_COMFORT_PASSWORD="..."
python3 client/mitsubishi.py login # stores tokens under ~/.config/mitsubishi (override: MITSUBISHI_CONFIG_DIR)
python3 client/mitsubishi.py status # find your unit's serial or name| Variable | Required | Meaning |
|---|---|---|
MITSUBISHI_COMFORT_EMAIL, MITSUBISHI_COMFORT_PASSWORD |
yes | Comfort app account; the password also enables automatic re-login when the refresh token expires |
MSC_DEVICE |
yes | Unit serial or name |
MSC_SENSOR_NAME |
no | Wireless sensor name, if the sensor is not linked to the unit |
MSC_LATITUDE, MSC_LONGITUDE |
no | Enables the outdoor temperature gate and the outdoor-adaptive cool target (Open-Meteo, no key needed). Without them the 73°F rule and the cool formula (on the 72.0°F fallback target) still work |
MSC_DATA_DIR |
no | Where state.json, log.csv and the heartbeat live (default ./var) |
MSC_INTERVAL_S |
no | Seconds between cycles (default 600) |
MSC_TIMEZONE |
no | IANA zone for log timestamps (default America/Los_Angeles, labelled PT; other zones are labelled with their key, e.g. UTC) |
MSC_CLIENT_CMD |
no | Command that runs the Comfort client (default python3 client/mitsubishi.py) |
MSC_CONFIG |
no | TOML config file (default ./config.toml if present) |
Every tuning value can also be set in a config file, and out-of-range values are rejected at startup; copy config.example.toml to config.toml. Environment variables win over the file. See .env.example for a template.
The controller writes its own log so you can chart your real results.
minisplit-controller --once --dry-run # decide and print, change nothing
minisplit-controller --once # one real cycle
scripts/run_loop.sh # detached loop, every 10 min, pidfile + heartbeat in MSC_DATA_DIR
scripts/restore.sh # stop the loop and put the unit back on stock Auto 67/73The loop sleeps in short chunks against the wall clock (it survives suspend and resume), caps each cycle with a watchdog, and logs a gap note when a cycle runs late. To start it at boot, use the systemd loop service or the @reboot cron entry in Pause resilience.
--once takes the same cycle lock as the loop, so it never overlaps a loop cycle (if a cycle is already running it prints another cycle is running; skipped, logs nothing and exits 0). --once --note TEXT adds TEXT to the cycle's log row, including an Error row. When a cycle is skipped or fails before it decides anything, --once prints the reason. It exits 2 when the cycle ends in an error (status read failed, command failed, crash or watchdog), else 0.
If the machine running the loop is paused, suspended or overloaded, cycles can be missed or the loop can die. scripts/kick.sh is a backup you run on a schedule (every 10 minutes is a good default). Each run does one of three things:
- Loop not running (no live process with
--loopon its command line inMSC_DATA_DIR/controller.pid): restart it withMSC_KICK_RESTART_CMD(defaultscripts/run_loop.sh 0). - Heartbeat missing or stale (
MSC_DATA_DIR/heartbeat.jsonabsent, or older thanMSC_KICK_STALE_S, default 720 s = 12 minutes; the loop rewrites it every 15 s while idle): run one cycle now with--once --note "kick: ...", under a hard timeout ofMSC_KICK_TIMEOUT_S(default 420 s = 7 minutes). Because--onceuses the loop's cycle lock, it cannot overlap a loop cycle. - Otherwise: nothing.
It prints one status line (ok, restarted, ran-cycle or error, with the reason, for example no heartbeat or the cycle's error) and exits 1 on error. A second copy started while one is running exits at once. After a kick cycle, the loop skips its own cycle if a cycle finished less than skip_recent_s ago and runs one interval after the kick cycle instead, so two cycles never run back to back.
Timeout rule: MSC_KICK_TIMEOUT_S must be greater than the cycle watchdog (cycle_watchdog_s, 360 s) plus 10 s, the time the controller allows the cloud client to exit (5 s after SIGTERM, then 5 s after SIGKILL). That lets a hung cycle hit its own watchdog and log the error before the outer timeout kills it. kick.sh refuses to run if the timeout is too small. If you raise cycle_watchdog_s, set MSC_KICK_WATCHDOG_S to the same value and raise MSC_KICK_TIMEOUT_S with it.
| Setting | Default | Where |
|---|---|---|
| Kick interval | 10 min | Your cron line or systemd timer |
MSC_KICK_STALE_S |
720 | Environment or .env (read by scripts/kick.sh) |
MSC_KICK_TIMEOUT_S |
420 | Environment or .env; must exceed MSC_KICK_WATCHDOG_S + 10 |
MSC_KICK_WATCHDOG_S |
360 | Environment or .env; keep equal to cycle_watchdog_s |
MSC_KICK_RESTART_CMD |
scripts/run_loop.sh 0 |
Environment or .env |
MSC_KICK_PYTHON |
python3 from PATH |
Environment or .env |
skip_recent_s / MSC_SKIP_RECENT_S |
300 | [controller] in the config file, or environment; clamped to half of interval_s at load |
kick.sh reads credentials and MSC_* settings from the environment or ./.env, like run_loop.sh, so a restarted loop can re-log in on its own. It needs flock and timeout (util-linux and coreutils on Linux).
cron (crontab -e), every 10 minutes. cron runs with a minimal PATH, so put your virtualenv first; both kick.sh and run_loop.sh then use its python3:
*/10 * * * * PATH=/path/to/mitsubishi-mini-split-controller/.venv/bin:/usr/bin:/bin /path/to/mitsubishi-mini-split-controller/scripts/kick.sh >> /path/to/mitsubishi-mini-split-controller/var/kick.log 2>&1Add an @reboot line that runs scripts/run_loop.sh the same way if cron also starts the loop at boot.
systemd (user units in ~/.config/systemd/user/): run the loop as its own service with Restart=always, and let a timer run kick.sh, which restarts that service instead of starting a loop of its own. Stopping the service stops the loop.
# minisplit-loop.service
[Unit]
Description=Mini-split controller loop
After=network-online.target
[Service]
WorkingDirectory=/path/to/mitsubishi-mini-split-controller
EnvironmentFile=-/path/to/mitsubishi-mini-split-controller/.env
Environment=PYTHONPATH=src
ExecStart=/path/to/mitsubishi-mini-split-controller/.venv/bin/python -u -m minisplit_controller --loop
Restart=always
RestartSec=30
[Install]
WantedBy=default.target# minisplit-kick.service
[Unit]
Description=Mini-split controller kick
[Service]
Type=oneshot
Environment=PATH=/path/to/mitsubishi-mini-split-controller/.venv/bin:/usr/bin:/bin
Environment="MSC_KICK_RESTART_CMD=systemctl --user restart minisplit-loop.service"
ExecStart=/path/to/mitsubishi-mini-split-controller/scripts/kick.sh# minisplit-kick.timer
[Unit]
Description=Run the mini-split controller kick every 10 minutes
[Timer]
OnBootSec=2min
OnUnitActiveSec=10min
[Install]
WantedBy=timers.targetsystemctl --user daemon-reload
systemctl --user enable --now minisplit-loop.service minisplit-kick.timer
loginctl enable-linger "$USER" # keep user services running when you are logged out
systemctl --user stop minisplit-kick.timer minisplit-loop.service # stop both (timer first, or the kick restarts the loop)With systemd, use systemctl --user stop rather than scripts/restore.sh to stop the loop, then run scripts/restore.sh to put the unit back on stock settings.
One row per cycle, plus an extra row for each regime, trim or setpoint change.
| Column | Meaning |
|---|---|
id |
Row number |
timestamp_pt |
Local time in MSC_TIMEZONE with a zone label (YYYY-MM-DD 7:20 AM PT) |
room_f |
Room temperature the controller used (°F) |
humidity |
Relative humidity reported by the unit (%) |
mode |
Unit mode after the cycle: heat, cool, auto, off |
auto_active |
In Auto mode, which side the unit was running (heat / cool); blank otherwise |
heat_sp, cool_sp |
Heat and cool setpoints on the unit (°F) |
fan |
Fan speed on the unit (quiet, low, powerful, superPowerful, or auto with staging off) |
event |
Reading (no change), Control change, or Error |
action |
What happened. Cycle rows start with outdoor ...; T ... Tp ... S ...F/h ... g ...m trim ... regime ... ctgt ... h2c ... fan e ... stage ... (ctgt is the cool target, or fallback without fresh outdoor data; h2c is the heat to cool threshold; fan e is the fan staging error, then the stage index and speed). In cool they add u ... want ... floor ... ctrim ... (the formula value, the setpoint it rounds to, the floor and the cool trim). When the sensor is the source they add udiff ... ema ... 6h ... (unit minus sensor offset, see Tuning) and a sensor offset alert note when the 6 h mean is out of range. Rows end with the changes sent |
room_c |
The unit's own room reading (°C) |
sensor_f |
Wireless sensor reading (°F), if available |
unit_f |
The unit's own room reading (°F) |
temp_source |
sensor or unit: which one room_f came from |
sensor_age_min |
Age of the sensor reading in minutes |
To chart your own log: python scripts/make_charts.py --from-log var/log.csv --out charts writes log-timeline and log-time-in-band (PNG and SVG) into charts/. Keep your log out of version control; it is under var/, which is git-ignored.
All values live in [tuning] in the config file.
Heat setpoint table (heat_table): Tp ≥ 70.6 → 66, ≥ 70.0 → 67, ≥ 69.4 → 68, ≥ 68.8 → 69, ≥ 68.2 → 70, else 71. Why these values: a mini-split heating in a small room overshoots its setpoint by a degree or more, so the setpoint has to sit below the target whenever the room is near it. Steps of 0.6°F in Tp map to 1°F of setpoint, which is the unit's own resolution, and the 66 to 71 range keeps it from ever blasting heat or shutting off for long.
Outdoor-adaptive cool target (adaptive_cool = true, cool_target_out_lo_f = 55, cool_target_out_hi_f = 80, cool_target_lo_f = 70.0, cool_target_hi_f = 73.5, cool_fallback_target_f = 72.0): with an outdoor reading at most outdoor_max_age_h (2 h) old, the room cool target is linear in outdoor temperature and held flat outside that range:
| Outdoor °F | ≤ 55 | 60 | 65 | 70 | 75 | ≥ 80 |
|---|---|---|---|---|---|---|
| Cool target °F | 70.0 | 70.7 | 71.4 | 72.1 | 72.8 | 73.5 |
Without a fresh outdoor reading (or with adaptive_cool = false) the target is cool_fallback_target_f, 72.0°F. Why these values: on a cold day a sunny room cools off quickly once the sun goes, so cooling can aim at the middle of the band without risk; on a hot day the walls and air stay warm, and aiming at 70°F would run the unit hard for little comfort gain. Without outdoor data the controller cannot tell a cold day from a hot one, so it aims at the top of the band.
Cool setpoint formula (cool_gain = 1.5, cool_floor_below_f = 1.5, cool_max = 78): Tp = room + 0.25 h × slope, then
- u = target + cool trim − 1.5 × (Tp − target), kept between the floor and 78
- floor = target − 1.5, rounded up: 69 on cold days (target 70.0), 72 on hot days (73.5), 71 without outdoor data (72.0)
- setpoint = u rounded to the nearest degree, halves up
At the target the unit is asked for the target itself; each 1°F over asks for 1.5°F colder, each 1°F under for 1.5°F warmer. Examples on a cold day (target 70.0, floor 69, trim 0): Tp 69.0 → 72, 69.5 → 71, 70.0 → 70, 70.5 and up → 69. On a hot day (target 73.5, floor 72): Tp 73.5 → 74, 75.0 and up → 72.
Cool hysteresis (cool_hyst_f = 0.75): on entering cool, or with no current cool setpoint, the setpoint is set straight to u rounded. After that it changes only when u is at least 0.75°F away from it. Raises happen at once; drops follow the rate limits below. Why: rounding alone would flip the setpoint by 1°F every time u crossed a half degree, and the unit reacts to each change; 0.75 means u has clearly moved before the unit hears about it.
Cool trim (cool_trim_band_f = 0.3, cool_trim_min = -2, cool_trim_max = 0; uses trim_every_h and trim_cover_h like the heat trim): every 3 hours in cool, if the last 3 hours have at least 2.5 hours of readings, compare the time-weighted mean with the cool target at that moment. More than 0.3°F above lowers the cool trim by 1; more than 0.3°F below raises it by 1. It stays within −2 to 0, is separate from the heat trim, and resets to 0 on entering cool. Why: a unit that idles at its setpoint can leave the room settling a degree or so above the target; the trim pulls u down slowly in that case and can never push it above the formula.
How the cool design got here. An outdoor-adaptive cool target came first, feeding a stepped setpoint table with a fixed floor. A later revision added a lower floor on cool days, because afternoons still ran 73 to 74°F while the floor capped cooling a degree or two higher. A stronger stepped table followed, about 2°F colder against the target, after the room sat 1 to 2°F above the target for hours while the controller asked for only a mild setpoint. That table still let the unit idle at the target while the room settled about 1.5°F high, so a short-lived version re-centered the setpoint on the target and added the measured offset between the unit's own sensor and the room sensor into the setpoint. A design review replaced it the same evening: the offset came back out of control (it is only logged now), the floor became a smooth function of the target instead of a jump at one outdoor temperature, the setpoint became the formula above with a 0.75°F hysteresis, and the slow cool trim took over the job of correcting a room that settles above the target. The two "low" fan stages were merged at the same time.
Unit vs sensor offset (unit_diff_alpha = 0.3, unit_diff_max_f = 3.0, unit_diff_window_h = 6.0, unit_diff_alert_f = 1.5): when the room reading comes from the wireless sensor, each cycle logs the unit's own reading minus the sensor reading, a smoothed value (EMA, weight 0.3, clamped to ±3°F), and its 6 h mean. When the 6 h mean is beyond ±1.5°F the log gets a sensor offset alert note. It has no effect on control. Why: a drifting or misplaced sensor shows up as a growing offset long before it shows up as discomfort, but feeding that offset into the setpoint made the loop harder to reason about.
Fan staging (fan_staging = true, fan_stages, fan_down_hyst_f = 0.3, fan_down_cycles = 2, fan_max_up = 2, fan_cool_target_default_f = 72.0): instead of leaving the fan on auto, the controller picks a speed from the error e. In cool, e = Tp minus the outdoor-adaptive cool target (72.0°F without a fresh outdoor reading). In heat, e = target_f (70°F) minus Tp. The first row with e ≤ threshold wins: ≤ 0.3 → quiet, ≤ 1.5 → low, ≤ 2.5 → powerful, else superPowerful. Rules:
- Step up immediately, at most 2 stages per cycle, so a jump from quiet can reach powerful in one cycle and superPowerful on the next.
- Step down only after e is at least 0.3°F below the lower stage's threshold on 2 consecutive cycles.
- After a gap over
gap_max_min(30 minutes) since the last good cycle, hold the unit's current speed. If the unit reports no speed and there is no saved stage yet, the fan falls back to the fixedfanvalue (defaultauto). - A fan command is sent only when the speed changes. The vane is never touched.
Why: staging keeps the unit quiet when the room is close and only pushes hard when it is clearly behind, and the hysteresis keeps the fan from hunting between speeds each cycle. An earlier default had five stages with low listed twice (≤ 0.8 and ≤ 1.5); they are now one stage. Saved state stores the stage as an index, so the first cycle after upgrading remaps a state file written before the change once (0 → 0, 1 → 1, 2 → 1, 3 → 2, 4 → 3) and records fan_stages_v = 2. The remap assumes the old five-stage default; if you had a custom fan_stages, the saved index may land one stage off for a cycle or two until the normal staging rules correct it. Speed names in fan_stages and fan are checked at config load against the speeds the Comfort client accepts (superQuiet, quiet, low, powerful, superPowerful, auto), and anything else is rejected with a config error. A particular unit may support fewer; the client rejects those when it sends. The client has no separate medium or high, so medium maps to low and high to powerful. Set fan_staging = false to go back to a fixed fan (default auto).
Breaking config changes. These [tuning] keys were removed with the cool formula: cool_table, cool_offsets, cool_offsets_else, cool_floor_table, cool_floor and cool_min. A config file that still sets one fails to load with tuning key '<name>' was removed: ... naming its replacement, rather than being silently ignored; delete the line and, if you had tuned it, use cool_fallback_target_f, cool_gain, cool_floor_below_f or cool_max instead. The fan_stages default changed from five rows to four (see Fan staging). Note that with outdoor data the lowest cool setpoint is now 69°F on cold days, where the older default stopped at 71°F.
Rate limits (step_min = 15, cool_big_err_f = 1.5, cool_big_step = 2, cool_fallback_target_f = 72.0): the risky direction (raising heat, lowering cool) moves at most once per 15 minutes; the safe direction moves at once. Heat rises 1°F per step. Cool drops 1°F per step, or 2°F when Tp is more than 1.5°F over the cool target (72.0°F when there is no fresh outdoor reading), and never past u rounded. Cool raises are immediate. Why: 15 minutes is roughly how long the room takes to show the effect of a change, so faster steps would stack up before they could be measured. The 2°F step is for the case where the room is clearly hot and 1°F per 15 minutes would take an hour to reach the setpoint the formula already asks for. cool_fallback_target_f (the cool target whenever there is no fresh outdoor reading, used by the formula, the floor and this step size) and the fan staging's fan_cool_target_default_f are independent settings that both default to 72.0°F; changing one does not change the other.
Trim limits (trim_every_h = 3, trim_deadband_f = 0.4, trim_min = -1, trim_max = 2): every 3 hours, if at least 2.5 hours of readings exist and the mean is more than 0.4°F off target, shift the table by 1°F. Why: 3 hours is long enough to average out a heating cycle, the deadband keeps it from hunting, and the asymmetric limits allow more correction on cold nights (heat loss) than on mild days, where a lower setpoint risks underheating.
The 73°F solar-gain rule (sun_override_f = 73, heat_to_cool_f = 73, heat_to_cool_margin_f = 1.5, heat_to_cool_hold_min = 20, sun_dwell_h = 1): switch to cool when the room holds at or above 73°F (or min(73, cool target + 1.5) with fresh outdoor data, so 71.5°F at 55°F or colder outside) for 20 minutes, at least 1 hour after the last switch, whatever the outdoor temperature. Why this value: with the heat setpoint already at its floor, the only thing that pushes a room past 73°F is solar gain. 73 is 2°F above the band, far enough that heating overshoot alone does not reach it, and the 20-minute hold filters out a single warm reading. The +1.5°F margin keeps the entry point 1.5°F above the cool target, so cooling starts only once the room is clearly past where it would settle, and on cold days it starts a little earlier, before the afternoon peak builds. Going back to heat needs 68°F held for 45 minutes and a 3-hour dwell, so a short cloud does not cause a flip.
Outdoor gate (outdoor_min_f = 62): the other way into cool needs outdoor air at 62°F or warmer and a 3-hour dwell. Why: on a warm day the room can drift up without sun, and requiring warm outdoor air plus the full 3-hour dwell keeps a brief warm spell on a cold day from starting a cooling cycle. 62°F is a starting point; adjust it for your climate.
Does this replace the Mitsubishi Comfort app or Kumo Cloud? No. It uses your Comfort account and the same Kumo Cloud backend, so the app keeps working and shows the settings the controller sends.
Why not just use Auto mode? Auto mode keeps a heat and a cool setpoint and only switches mode when the room crosses the other one, so the room can sit away from the target for long stretches. This controller stays in heat, adjusts the setpoint from a 15-minute temperature prediction, aiming to limit overshoot, and only cools for solar gain. See The problem.
Are the charts real measurements? No. They are an illustrative simulation (scripts/simulate.py). The controller logs every cycle so you can chart your own results with --from-log.
Does it work with MELCloud? No. Only the Comfort app / Kumo Cloud cloud is implemented.
Does it save energy? Unknown. Energy use has not been measured. In simulation it cools for fewer hours than a 70/72 Auto, but that is not a measured saving.
What happens if the cloud or my internet goes down? The unit keeps its last settings. The controller never turns a unit on and leaves an off or offline unit alone.
How do I undo it? Run scripts/restore.sh, which stops the loop and sets the unit back to stock Auto 67/73.
Can I use Celsius? All targets and tables are in °F. How it behaves with a Comfort account set to °C has not been verified.
- Unofficial. This project is not affiliated with or endorsed by Mitsubishi Electric. It uses the same cloud API as the Mitsubishi Comfort app, which is undocumented and can change or break at any time.
- Cloud dependent. Every reading and command goes through Mitsubishi's servers. If the cloud or your internet is down, the unit simply keeps its last settings. The client backs off when rate limited and re-logs in at most once per 10 minutes.
- Conservative by design. The controller never turns a unit on, never changes the vane, and leaves a switched-off or offline unit alone. Setpoints are clamped to 66 to 71°F for heat and, for cool, from the floor (69 to 72°F with a fresh outdoor reading, 71°F without) to 78°F by default, and the config loader rejects values outside safe ranges (no cool floor below 64°F, no cool maximum above 88°F).
- Simulated charts. The README charts come from a simulation, not measurements. Your room, unit and climate will differ, so tune and watch the log.
- No warranty. Use at your own risk; see the license.
The bundled client in client/mitsubishi.py credits the open-source projects whose protocol notes it follows in its header.
MIT © 2026 Chris Perish