simharness plant mode: CHW/HW FPR via DOE prototypes + DCV preconditions (#32)
Plant-loop discovery/mapping/gating for --mode plant; DOE prototype IDFs
enter via the E+ 22.1->25.1 transition chain + ConvertInputFormat. First
plant sweep (OfficeLarge STD2019 Atlanta, Jul+Jan): CHW-FC-053 and
HW-FC-052/053/054 clean in gated windows — validation: blocks recorded,
first empirical validation outside the AHU family. HW-FC-056 verified
firing correctly on the prototype's constant-HWST-at-low-load operation
(excluded by-construction with reason). DCV-aware NO_EVAL precondition
added to AHU-FC-006/055 per the fleet-sweep finding.
Co-authored-by: Claude Fable 5 <noreply@anthropic.com>
operating_states: "OS#1 and OS#4 (minimum outdoor air states) — host-gated"
25
-
preconditions: "Supply fan running, and the unit in one of the two minimum-OA operating states G36 defines by actuator signature: OS#1 (HC > 0, CC = 0, OA damper at minimum) or OS#4 (HC = 0, CC > 0, OA damper at minimum). The rule must not be evaluated in OS#2 or OS#3, where the outdoor-air fraction is supposed to exceed the minimum — economizing looks identical to a stuck damper from these three temperatures — nor in OS#5, where no damper position is defined at all. Suspend evaluation for ModeDelay (30 min) after any mode or operating-state change in a zone group the AHU serves, while the dampers are still stroking and the mixing box has not settled. Silence the rule while AHU-FC-062 is active: the fraction is a ratio of temperature differences, so a MAT outside the OAT/RAT envelope moves it directly. `min_oa_fraction` must be retuned to track the active minimum-OA setpoint whenever the ventilation reset moves it (see Deviations). The temperature-difference conjunct is signalled in-rule by yTempDeltaOk; when it is false the verdict is NO_EVAL, not healthy, and the same is true whenever any of the gates above is unmet."
25
+
preconditions: "Supply fan running, and the unit in one of the two minimum-OA operating states G36 defines by actuator signature: OS#1 (HC > 0, CC = 0, OA damper at minimum) or OS#4 (HC = 0, CC > 0, OA damper at minimum). The rule must not be evaluated in OS#2 or OS#3, where the outdoor-air fraction is supposed to exceed the minimum — economizing looks identical to a stuck damper from these three temperatures — nor in OS#5, where no damper position is defined at all. Suspend evaluation for ModeDelay (30 min) after any mode or operating-state change in a zone group the AHU serves, while the dampers are still stroking and the mixing box has not settled. Silence the rule while AHU-FC-062 is active: the fraction is a ratio of temperature differences, so a MAT outside the OAT/RAT envelope moves it directly. `min_oa_fraction` must be retuned to track the active minimum-OA setpoint whenever the ventilation reset moves it (see Deviations). The temperature-difference conjunct is signalled in-rule by yTempDeltaOk; when it is false the verdict is NO_EVAL, not healthy, and the same is true whenever any of the gates above is unmet. Additionally suspend evaluation (NO_EVAL) while demand-controlled ventilation or a ventilation-demand override holds outdoor-air flow above the minimum-OA state — at VAV turndown a constant ventilation flow becomes a large OA fraction and this rule fires on healthy operation (fleet-validated FP mechanism; see the validation block)."
Copy file name to clipboardExpand all lines: faults/ahu/AHU-FC-055/card.md
+1-1Lines changed: 1 addition & 1 deletion
Display the source diff
Display the rich diff
Original file line number
Diff line number
Diff line change
@@ -21,7 +21,7 @@ suppressed_by: [AHU-FC-062]
21
21
related: [AHU-FC-006, AHU-FC-051, AHU-FC-064]
22
22
playbooks: [economizer-failure]
23
23
operating_states: "occupied, non-economizer operation (host-gated); reference OS 1, OS 4"
24
-
preconditions: "Supply fan running. The host must not evaluate during economizer operation — bringing in more than the design minimum is the point of economizing, and this rule cannot tell that apart from a stuck damper. MAT must pass its integrity gate (AHU-FC-062, see suppressed_by): the fraction is a ratio of temperature differences, so a biased mixed-air reading moves it directly. The temperature-difference gate is signalled in-rule by yTempDeltaOk; when it is false the verdict is NO_EVAL, not healthy."
24
+
preconditions: "Supply fan running. The host must not evaluate during economizer operation — bringing in more than the design minimum is the point of economizing, and this rule cannot tell that apart from a stuck damper. MAT must pass its integrity gate (AHU-FC-062, see suppressed_by): the fraction is a ratio of temperature differences, so a biased mixed-air reading moves it directly. The temperature-difference gate is signalled in-rule by yTempDeltaOk; when it is false the verdict is NO_EVAL, not healthy. Additionally suspend evaluation (NO_EVAL) while demand-controlled ventilation or a ventilation-demand override holds outdoor-air flow above the minimum-OA state — at VAV turndown a constant ventilation flow becomes a large OA fraction and this rule fires on healthy operation (fleet-validated FP mechanism; see the validation block)."
"CHW-FC-050": "host-fitted kW/ton baseline placeholders — needs a per-plant fit first",
315
+
"CHW-FC-051": "reset-class: prototype uses a constant scheduled CHW setpoint, fires by construction",
316
+
"HW-FC-050": "host-fitted baseline placeholders — needs a per-plant fit first",
317
+
"HW-FC-051": "host-fitted baseline placeholders — needs a per-plant fit first",
318
+
"HW-FC-057": "reset-class: constant scheduled HW setpoint, fires by construction",
319
+
"HW-FC-056": "by-construction: constant HWST at low evening load IS the retuning condition it detects (no HWST reset in the prototype); verified firing correctly, Jan week",
0 commit comments