Tower groundwork: condenser-loop stats + 4-climate plant fleet validation - #35
Merged
Conversation
…tion Plant mode maps the condenser loop (tower water temps, fan power, native E+ wet-bulb) and emits per-run approach/range percentiles. Four-climate OfficeLarge sweep (Miami/Tucson/Atlanta/Buffalo x Jul+Jan): every eligible CHW/HW rule clean in all 8 runs — validation entries appended. Healthy approach spans 1.6-13.3 degC across climates/seasons (VFD fan modulation), so the future TOWER family's approach rule must gate on fan-at-capacity, not a fixed threshold; range is stable (p50 2.2-3.2) making range-collapse a viable second rule. Full design note local. Co-Authored-By: Claude Fable 5 <noreply@anthropic.com>
This file contains hidden or bidirectional Unicode text that may be interpreted or compiled differently than what appears below. To review, open the file in an editor that reveals hidden Unicode characters.
Learn more about bidirectional Unicode characters
Sign up for free
to join this conversation on GitHub.
Already have an account?
Sign in to comment
Add this suggestion to a batch that can be applied as a single commit.This suggestion is invalid because no changes were made to the code.Suggestions cannot be applied while the pull request is closed.Suggestions cannot be applied while viewing a subset of changes.Only one suggestion per line can be applied in a batch.Add this suggestion to a batch that can be applied as a single commit.Applying suggestions on deleted lines is not supported.You must change the existing code in this line in order to create a valid suggestion.Outdated suggestions cannot be applied.This suggestion has been applied or marked resolved.Suggestions cannot be applied from pending reviews.Suggestions cannot be applied on multi-line comments.Suggestions cannot be applied while the pull request is queued to merge.Suggestion cannot be applied right now. Please check back later.
Plant mode maps the condenser loop (tower water temps, fan power, native
E+ wet-bulb) and emits per-run approach/range percentiles. Four-climate
OfficeLarge sweep (Miami/Tucson/Atlanta/Buffalo x Jul+Jan): every
eligible CHW/HW rule clean in all 8 runs — validation entries appended.
Healthy approach spans 1.6-13.3 degC across climates/seasons (VFD fan
modulation), so the future TOWER family's approach rule must gate on
fan-at-capacity, not a fixed threshold; range is stable (p50 2.2-3.2)
making range-collapse a viable second rule. Full design note local.
Co-Authored-By: Claude Fable 5 noreply@anthropic.com