@@ -45,6 +45,10 @@ Modbus read, a timer is armed: if reads are still failing once that many seconds
4545the last success, the add-on pauses normal polling for that inverter for the configured skip period,
4646then probes the serial register once before resuming or extending stale quiet.
4747
48+ A parallel AC setup (inverter ** Parallel Mode** Client / Server) does ** not** mean both inverters
49+ share the RS485 Modbus bus. If the second inverter never appears, see
50+ [ Parallel inverters] ( #parallel-inverters ) below.
51+
4852If you fail to get a reply from the inverter, typically if step #2 fails, please check the
4953following:
5054
@@ -149,3 +153,40 @@ RS485 devices are typically multi-drop with a termination resistor on the first
149153However, the RS485 BMS port may only be intended to connect to a single device.
150154
151155![ RS485] (../images/rs485-term.jpg =70%x)
156+
157+ ## (D) Parallel inverters — second inverter not responding {#parallel-inverters}
158+
159+ The add-on can poll several inverters on ** one** adaptor when they share a physical RS485 bus: same
160+ ` PORT ` , unique ` MODBUS_ID ` (and ` SERIAL_NR ` / ` HA_PREFIX ` ) per unit. See
161+ [ Shared RS485 bus] ( ../reference/multi-options#port ) .
162+
163+ Parallel Mode does ** not** automatically daisy-chain Modbus. If only one inverter answers, or the
164+ other goes ** stale** / startup shows no response, test ** one inverter at a time** with the ** same**
165+ USB adaptor. Change only which RJ45 you plug into and the single ` INVERTERS ` entry. The inverter LCD
166+ may still say Master / Slave for Parallel Mode; this add-on uses ** Client** / ** Server** . See
167+ [ Modbus] ( ./overview.md#modbus ) .
168+
169+ 1 . ** Baseline — inverter 1 only.** Plug the cable into inverter 1. Configure one ` INVERTERS ` entry
170+ for that unit (` MODBUS_ID ` matching its ** Modbus SN** ). If this fails, it is a normal connection
171+ problem — follow (A)–(C).
172+
173+ 2 . ** Inverter 2 on its own socket.** Move the ** same** cable to inverter 2. Change the config to
174+ inverter 2 only (` HA_PREFIX ` , ` MODBUS_ID ` , ` SERIAL_NR ` ). If this fails while plugged into
175+ inverter 2, inverter 2 is not answering Modbus: check its Modbus SN, cabling, and whether that
176+ model exposes RS485 on the port you are using when Parallel Mode is Server.
177+
178+ 3 . ** Is the bus shared?** Plug the cable back into inverter 1. Keep the ** inverter 1** config. Then
179+ move the cable to inverter 2 ** without changing the config** .
180+
181+ - If inverter 1 still answers with the cable on inverter 2, the RS485 bus ** is** shared — use the
182+ ** same** ` PORT ` for both ` INVERTERS ` entries, with unique ` MODBUS_ID ` s.
183+ - If it goes silent, the bus is ** not** shared. Use ** two adaptors** (two ` PORT ` s), one per
184+ inverter.
185+
186+ 4 . ** Optional cross-check.** Cable on inverter 1, config for inverter 2 only. A reply means inverter
187+ 2 is reachable through inverter 1's socket (shared bus). No reply means the bus is not shared, or
188+ inverter 2's ` MODBUS_ID ` is wrong.
189+
190+ When using two adaptors, ` MODBUS_ID ` must match whatever unit actually answers on ** that** adaptor.
191+ Some units in Server mode still answer as ` 1 ` on their own RS485 port even when the display shows a
192+ different Modbus SN.